asecos Battery Storage Cabinet Battery Charge / ION-CHARGE 90 with sliding levels
- Automatic locking
- Certified as Type 90 according to EN 14470-1
- 8 outlets at 230 V
Do you have some questions about this product?
- Your personal contact person
- Name: Petra Fürbeck
- E-Mail: info@lion-care.com
- Phone: +49 (0) 7151 - 256 4817
Technical data
| Alarm forwarding: | Yes |
|---|---|
| Fire resistance: | 90 min |
| Fire suppression: | Without |
| Fire test procedure: | DIN EN 1363-1, DIN EN 14470-1 |
| Internal dimensions (mm): | 470 x 452 x 582 |
| Load function: | Yes |
| Number of drawers: | 1 |
| Number of shelves: | 2 |
| Outer dimensions (mm): | 593 x 574 x 780 |
| Place of deployment: | Indoor area |
| Power supply: | 2 bars of 4 x 230 V |
| Refractory: | Yes |
| Wardrobe type: | Under-sink cabinet |
| Weight (kg): | 130 |
Product information „asecos charging cabinet Battery Charge / ION-CHARGE 90 with sliding levels“
asecos ION-LINE – Safe cabinet for lithium-ion batteries
1. Product overview
The safety cabinets of the ION-LINE from asecos offer a tested solution for the safe storage and optionally for charging lithium-ion batteries. The cabinets meet important requirements of insurers and associations and enable controlled and fire-protected storage of lithium batteries in a business environment.
With proven fire protection both from inside to outside and from outside to inside, the ION-LINE models are suitable for companies that want to store or charge lithium batteries professionally and with minimized risk. Thanks to their compact design, the safety cabinets can be integrated into existing work areas without complex alterations.
2. Areas of use & application
-
Safe storage of lithium-ion batteries and cells
-
Charging of batteries depending on model variant
-
Suitable for batteries from power tools, industrial applications, e-mobility and crafts
-
Used in workshops, production areas, storage rooms and technical work environments
-
Integration into existing buildings possible without structural changes
To meet insurance requirements, it is recommended to set up an alarm forwarding to a continuously staffed location.
3. Technical data – asecos ION-LINE battery safety cabinet
- External dimensions (H x W × D): 780 x 593 × 574 mm
- Internal dimensions (H x W × D): 470 × 452 × 582 mm
- Net weight: ca. 130 kg
- Maximum total load: ca. 300 kg
- 2 pull-out levels, load capacity per 25 kg
- Drawer tray, load capacity 50 kg
- Floor catch tray made of sheet steel
- 2 power strips (EU version)
Available internal dimensions may vary depending on the chosen interior equipment.
4. Direct comparison of the variants
| CORE STORE Battery cabinet | PRO STORE Battery cabinet | CORE CHARGE or ION CHARGE Battery cabinet | PRO CHARGE Battery cabinet | ULTRA Battery cabinet | |
| Fire protection | 90 min inside and outside, EN 14470-1, EN 1363-1 | 90 min inside and outside EN 14470-1, EN 1363-1, VDMA 24994 | 90 min inside and outside EN 14470-1, EN 1363-1 | 90 min inside and outside EN 14470-1, EN 1363-1, VDMA 24994 | 90 min inside and outside EN 14470-1, EN 1363-1, VDMA 24994, GS mark: EK5/AK4 22-01 |
| Bottom tray | Integrated bottom tray made of sheet steel | ||||
| Warning system | 1-stage including smoke detector and potential-free contact | 3-stage, including smoke detector, temperature sensor, optical & acoustic alarm, potential-free contact | 1-stage incl. smoke detector and potential-free contact | 3-stage, including smoke detector, temperature sensor, optical & acoustic alarm, potential-free contact | 3-stage, including smoke detector, temperature sensor, optical & acoustic alarm, relay module with 4 separate potential-free contacts |
| Fire suppression system | Not present | Optional | Not present | Optional | Optional |
| Charging option | Not available | 230V sockets on the shelf floors / in the compartments | |||
5. Materials & construction
The safety cabinet features a robust outer casing with scratch-resistant powder coating and a durable structural surface.
-
Powder-coated steel cabinet
-
Corrosion-protected locking mechanism
-
Safety elements mounted outside the storage space
-
Interior equipment made of powder-coated steel sheet
-
Standard color of interior equipment:
-
RAL 5010 Gentian blue
-
RAL 7035 Light gray
-
The integrated transport base enables easy intra-company transport.
6. Fire protection and safety features
The ION-LINE safety cabinets provide comprehensive fire protection for lithium-ion batteries.
-
Fire resistance: 90 minutes
-
Fire protection from outside to inside according to EN 14470-1
-
Fire resistance from inside to outside according to EN 1363-1
-
Self-closing drawer in case of fire
-
Lockable drawer with cylinder lock
-
Door state display (red/green)
-
Earthed cable with clamp for electrostatic discharge
The integrated bottom tray is StawaR tested.
7. Charging and connection options
Depending on model variant, lithium batteries can be charged directly in the cabinet.
-
Power strips inside (EU version)
-
Suitable for simultaneous charging of multiple batteries
-
Active exhaust fan to ventilate the interior
-
Potential-free contact for alarm forwarding to a monitoring center
Optional is a telemetry module that informs the plant manager in case of an alarm.
For effective protection, a 24/7 alarm forwarding is recommended.
8. Standards, tests & maintenance
Certifications
-
Fire resistance 90 minutes
-
Type-tested according to EN 14470-1
-
Fire test according to EN 1363-1
-
CE conformity
Maintenance
The warranty period for the ION-LINE safety cabinets is 24 months.
According to:
-
Workplace Ordinance (ArbStättV)
-
TRGS 526
Safety cabinets must be regularly maintained. The recommended maintenance interval is maximum 12 months.
The first maintenance by the manufacturer's service is required after 12 months to maintain the warranty.
9. Manufacturer – asecos
The manufacturer asecos is one of the leading providers of safety cabinets in Germany. About 300 employees work on the development and production of solutions for the safe storage of hazardous substances.
In addition to an extensive product portfolio, asecos offers:
-
Maintenance and service
-
Consultation by trained specialists
-
Support with legal requirements and safety concepts
The goal is to sustainably improve the protection of people, the environment and workplaces.
10. For you in operation
When you have questions, please feel free to contact us.
We look forward to hearing from you!
| Alarm forwarding: | Yes |
|---|---|
| Fire resistance: | 90 min |
| Fire suppression: | Without |
| Fire test procedure: | DIN EN 1363-1, DIN EN 14470-1 |
| Internal dimensions (mm): | 470 x 452 x 582 |
| Load function: | Yes |
| Number of drawers: | 1 |
| Number of shelves: | 2 |
| Outer dimensions (mm): | 593 x 574 x 780 |
| Place of deployment: | Indoor area |
| Power supply: | 2 bars of 4 x 230 V |
| Refractory: | Yes |
| Wardrobe type: | Under-sink cabinet |
| Weight (kg): | 130 |
Downloads
FAQ
Standard security cabinets are designed for indoor use, so they cannot be used outdoors.
The fire protection panels installed in the cabinets contain gypsum, which contains a lot of water, which expands when frozen. This deforms the panels. It can no longer be guaranteed that such a cabinet is still sealed or can withstand an explosion.
If you already have a suitable room that is structurally fire-resistant, then you do not necessarily need a safety cabinet to contain the fire.
However, please do not forget that the damage caused by a battery fire involves immense and also toxic contamination, the disposal of which can quickly lead to high costs.
In addition, you may not be able to continue working as usual until the damage has been finally repaired - depending on the location of the damage.
Accessory
Standard security cabinets are designed for indoor use, so they cannot be used outdoors.
The fire protection panels installed in the cabinets contain gypsum, which contains a lot of water, which expands when frozen. This deforms the panels. It can no longer be guaranteed that such a cabinet is still sealed or can withstand an explosion.
If you already have a suitable room that is structurally fire-resistant, then you do not necessarily need a safety cabinet to contain the fire.
However, please do not forget that the damage caused by a battery fire involves immense and also toxic contamination, the disposal of which can quickly lead to high costs.
In addition, you may not be able to continue working as usual until the damage has been finally repaired - depending on the location of the damage.