- Includes smoke detectors and potential-free contact
- Certified as Type 90 according to EN 14470-1
- Automatically self-closing doors
Do you have some questions about this product?
- Your personal contact person
- Name: Petra Fürbeck
- E-Mail: info@lion-care.com
- Phone: +49 (0) 7151 - 256 4817
Technical data
| Alarm forwarding: | Yes |
|---|---|
| Cabinet type: | Freestanding cabinet |
| Charging function: | No |
| Fire resistance: | 90 min |
| Fire suppression: | Without |
| Fire test procedure: | DIN EN 1363-1, DIN EN 14470-1 |
| Internal dimensions (mm): | 1 050 x 503 x 1 647 |
| Number of doors: | 2-leaf hinged |
| Number of drawers: | 0 |
| Number of shelves: | 3, 4, 5, 6 |
| Outer dimensions (mm): | 1 193 x 615 x 1953 |
| Place of deployment: | Indoor area |
| Power supply: | without |
| Refractory: | Yes |
| Weight (kg): | 476 |
Product information „asecos Lagerschrank CORE STORE / ION-CORE-90 (2-flg.)“
1. Product overview
The asecos CORE STORE safety cabinet from the ION-LINE range has been developed for the safe, passive storage of lithium-ion batteries. With its certified fire resistance and robust construction, the cabinet supports a secure safety concept for businesses that store lithium batteries in workshops, production areas or technical rooms.
An integrated LED display in the top section of the cabinet allows operating statuses and alarm messages to be viewed directly on the unit. In addition, audible signals ensure that faults, alarms or malfunctions are noticed immediately.
The cabinet offers over 90 minutes of fire resistance both from the outside in and from the inside out, thereby meeting key requirements for workplace fire safety.
Note: Images may differ from the product supplied.
2. Areas of use & application
-
Passive storage of lithium-ion batteries
-
Use in workshops, industry and technical areas
-
Organisation of large battery stocks across multiple storage levels
-
Integration into existing spaces without structural alterations
The CORE STORE is designed solely for the storage of batteries and does not have an integrated charging function.
3. Technical data – asecos CORE STORE
External dimensions (W × D × H): 1,193 × 615 × 1,953 mm
Internal dimensions (W × D × H): 1 050 × 522 × 1 647 mm
Empty weight: approx. 476 kg
Maximum total load: approx. 600 kg
Interior fittings
-
3 / 4 / 5 / 6 thermally insulated shelves
-
Load capacity per shelf: 75 kg
-
Floor drip tray made of powder-coated sheet steel
The usable internal dimensions may vary depending on the interior fittings.
4. Direct comparison of the variants
| CORE STORE battery cabinet | PRO STORE battery cabinet | CORE CHARGE or ION CHARGE battery cabinet | PRO CHARGE battery cabinet | ULTRA battery cabinet | |
| Fire protection | 90 minutes internally and externally, EN 14470-1, EN 1363-1 | 90 minutes internally and externally, EN 14470-1, EN 1363-1, VDMA 24994 | 90 minutes inside and outside, EN 14470-1, EN 1363-1 | 90 mins internally and externally, EN 14470-1, EN 1363-1, VDMA 24994 | 90 min internal and external EN 14470-1, EN 1363-1, VDMA 24994, GS mark: EK5/AK4 22-01 |
| Base tray | Integrated base tray made of sheet steel | ||||
| Warning system | 1-stage, including smoke detector and potential-free contact | 3-stage, including smoke detector, temperature sensor, visual and audible alarms, potential-free contact | 1-stage, including smoke detector and potential-free contact | 3-stage, including smoke detector, temperature sensor, visual & audible alarms, potential-free contact | 3-stage, including smoke detector, temperature sensor, visual and audible alarms, relay module with 4 separate potential-free contacts |
| Fire suppression system | Not available | Optional | Not available | Optional | Optional |
| Charging option | Not available | 230V sockets on the shelves / in the lockers | |||
5. Materials & Construction
The security cabinet is robustly constructed for professional use.
-
Sturdy outer body with a powder-coated textured finish
-
Triple door hinges
-
Corrosion-protected locking mechanism located outside the storage compartment
-
Shelves made from powder-coated sheet steel
-
Colour of interior finish: RAL 7035 Light Grey
Integrated levelling feet allow for compensation of uneven floors.
6. Fire protection and safety features
The CORE STORE safety cabinet offers a certified fire protection concept for lithium-ion batteries.
-
Fire resistance for over 90 minutes
-
Fire protection from the outside in accordance with EN 14470-1 (Type 90)
-
Fire resistance from the inside out in accordance with EN 1363-1
-
Thermally insulated shelves to reduce the spread of fire
-
Automatically self-closing doors
- LED display to indicate operating states and alarms
- Additional audible alarm signals in the event of faults and hazards
- Door contact switch with an alarm if the door remains open for more than 60 seconds
- Power failure alert with visual and audible alarms
- Battery backup of approx. 120 minutes to maintain alarm functions during a power cut
In the event of a fire, the shelving prevents the spread of batteries or cells to adjacent storage levels.
7. Ventilation & technical features
The safety cabinet is fitted with an integrated ventilation system.
-
Air intake and exhaust system with connection option (NW 75) to a technical exhaust air
-
Rotating indicator wheel in the exhaust grille to monitor ventilation
A 230 V mains connection is required
Country-specific mains connection cable included in the scope of delivery
In addition, the cabinet has a potential-free contact for connection to a permanently manned control centre. Optionally, a remote signalling module can be used to alert the site manager.
8. Standards, Testing & Delivery
Certifications
-
EN 14470-1: Fire resistance 90 minutes (Type 90)
-
EN 1363-1: Fire resistance from the inside to the outside
Delivery
The asecos ION-LINE models are delivered to the point of use
.
A transport questionnaire is provided prior to delivery to ensure a smooth delivery process.
9. Manufacturer – asecos
The manufacturer, asecos, develops safety cabinets for hazardous substances and lithium batteries. Around 300 employees work on solutions for safe workplaces in industry, laboratories and technical areas.
In addition to development and production, asecos also offers:
-
Maintenance and servicing
-
Technical advice
-
Support with regulatory requirements
The company’s aim is to provide the highest possible level of protection for people, the environment and working environments.
10. Working for you
Please do not hesitate to contact us if you have any queries.
We look forward to hearing from you!
| Alarm forwarding: | Yes |
|---|---|
| Cabinet type: | Freestanding cabinet |
| Charging function: | No |
| Fire resistance: | 90 min |
| Fire suppression: | Without |
| Fire test procedure: | DIN EN 1363-1, DIN EN 14470-1 |
| Internal dimensions (mm): | 1 050 x 503 x 1 647 |
| Number of doors: | 2-leaf hinged |
| Number of drawers: | 0 |
| Number of shelves: | 3, 4, 5, 6 |
| Outer dimensions (mm): | 1 193 x 615 x 1953 |
| Place of deployment: | Indoor area |
| Power supply: | without |
| Refractory: | Yes |
| Weight (kg): | 476 |
Downloads
FAQ
Standard security cabinets are designed for indoor use, so they cannot be used outdoors.
The fire protection panels installed in the cabinets contain gypsum, which contains a lot of water, which expands when frozen. This deforms the panels. It can no longer be guaranteed that such a cabinet is still sealed or can withstand an explosion.
If you already have a suitable room that is structurally fire-resistant, then you do not necessarily need a safety cabinet to contain the fire.
However, please do not forget that the damage caused by a battery fire involves immense and also toxic contamination, the disposal of which can quickly lead to high costs.
In addition, you may not be able to continue working as usual until the damage has been finally repaired - depending on the location of the damage.
Standard security cabinets are designed for indoor use, so they cannot be used outdoors.
The fire protection panels installed in the cabinets contain gypsum, which contains a lot of water, which expands when frozen. This deforms the panels. It can no longer be guaranteed that such a cabinet is still sealed or can withstand an explosion.
If you already have a suitable room that is structurally fire-resistant, then you do not necessarily need a safety cabinet to contain the fire.
However, please do not forget that the damage caused by a battery fire involves immense and also toxic contamination, the disposal of which can quickly lead to high costs.
In addition, you may not be able to continue working as usual until the damage has been finally repaired - depending on the location of the damage.